- 6 zone leak detection panel with optional battery back-up (up to 24 or 6 hours)
- Simultaneously detects leaks on all 6 zones
- 30 metres per zone (EcoLeak Cable) or up to 60 metres with the ECO-BCB
- 160 metres per zone (TraceTek Cable)
- Detection Probes: 1x EL-MPS-R probe, per zone (2 per zone using ECO-BCB)
- 10x AT-PROBE-TS (TT-FLAT-PROBE), 10 x AT-OPSEN or 1x AT-SRG
- Compact design suits installation in utility cupboards, plant and boiler rooms, bathrooms, kitchens and air conditioning/fan coil unit drip trays
- Individual leak and cable break LED display for each zone
- Leak, Cable break (fault) alarms and remote sounder relays
- Six individual ‘Leak Detected’ volt free relays, one per zone for connection to a BMS and/or individual solenoid valves or other remote monitoring systems
- Additionally; 1 Common Cable break/fault relay, plus a dedicated remote sounder relay for connection to a BMS, auto dialler or home automation system
- New Eco-Network connector allowing multiple EcoLeak panels to be connected in a network and reporting back to one master EcoLeak panel for even more connectivity
- 12Vdc powered auxiliary output for use with AT-OPSEN sensors, AT-SRG refrigerant sensor, sounder/beacons, remote alarms (max 500mA)
- 110 to 240Vac and battery back-up operation
- Suitable for sensing leaks for water, hydrocarbon fuels and chemicals using sensing cable or water, fuel or refrigerant gas sensing probes
- Audible alarm (90dB@ 10cm)
- IP43 steel lockable enclosure
|
Click for Datasheet
Installation Instructions
Wiring instruction video
|