Alarm Water Oil Chemical Refrigerant
Leak Detection and Locating Systems


Single Wall, Buried Pipelines on Airport

The danger of environmental contamination and the potential repair costs of an undetected fuel leak along an airport kerosene pipeline can be astronomical.

To reduce this risk of environmental contamination, TraceTek monitors hundreds to thousands of meters of single wall buried pipelines and provides the exact location of any developing small leaks.

An interface to the monitoring control center or BMS receives the notification and displays the distance to the leak.
The exact location allows quick reaction whilst the leak is still small, helping to prevent larger spills.

Under streets or other barriers it is installed in a coated pipe.

Components

Amount
Catalogue Number
Description
1 pc
TTDM-128
Alarm and Locating Module
1 pc
TTSIM-1
Sensor Interface Module
ca. 500 m
TT5000
Fuel Sensing Cable
ca. 60 m
TT-JC-BLK-HS
Jumper Cable
1 pc
TT-MBC-MC-BLK
Modular Branch Connector
2 pcs
TT-MET-MC
Modular End Terminator
600 m
TT-PR
Pull Rope
500 m
Slit Conduit with Accessories
6 pcs
Connecting Box
TraceTek Leak Detection and Locating System in a NATO-Airbase close to Prague in Czech Republic.
Tracetek Sensor cables are installed parallel to the pipeline by pulling through the permeable blue conduit shown.


TraceTek TT5000 Sensing Cable installed inside slotted PVC conduit along side a single wall buried pipeline can detect a small fuel leak and identify the location with pinpoint accuracy. Traces of any fuel leakage are drawn into the conduit by capillary action and contact the sensing cable for detection and location of the leak.



Approvals
 
Sensing cable may be used in Class I, Division 2, Groups A, B, C, D Hazardous Locations. If wiring from module meets requirements for intrinsic safety, sensing cable may be used in Class I, Division 1, Groups A, B, C, and D Hazardous Locations (Zone 0 or Zone 1 in Europe).
The TraceTek products group is a part of Tyco Thermal Controls.
Tyco Thermal Controls is ISO 9001 Certified.

Third Party Test & Evaluation
Carnegie Mellon Research Institute
"Test Procedures for Third Party Evaluation of Leak Detection Methods: Cable Sensor Liquid Contact Leak Detection Systems"
Ken Wilcox Associates, Inc
"Evaluation of the TraceTek TT5000 Product Sensitive Cable For use as a Leak Detection System For Buried Pipelines"
State of Florida Department of Environmental Protection Approval of the TraceTek TT5000 Leak Detection System for Single-Walled Underground Bulk Product Piping File No. EQ-551


Important:
All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranty as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls’ only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification.

Tyco and TraceTek are trademarks or registered trademarks of Tyco Thermal Controls LLC or its affiliates.

 

Datasheets


Protect your network
- don't wait until it's too late

Aquilar Ltd
TraceTek Master Distributor
Weights & Measures House
20 Barttelot Road
Horsham
West Sussex
RH12 1DQ
United Kingdom

TTel: + 44 (0) 1403 216100
Tel: + 44 (0) 8707 941 310
Fax: +44 (0) 8707 940320
Click here to email Aquilar


TraceTek products are manufactured by Tyco Thermal Controls LLC

 

 

 

 

 ©Aquilar Ltd. All rights reserved | Privacy Policy | Links