Aquilar Ltd - A complete leak detection solution.


Frequently Asked Questions

Welcome to our Frequently Asked Questions (FAQ) section.

::
When should I use a probe instead of water sensing cable?
::
Probe allows the monitoring of leaks in areas where sensing cables would be difficult to install, either because of the harsh operating environment or if the area is wet or damp like the base of a lift pit or in plant areas.

::
What sort of layout do I need for a computer room / Comms room?
::
A typical layout would be to cover the inner perimeter of the room in front of any air conditioning units, covering the main central area of the floor is optional depending if there are any water services in that area.
Click here to down load a copy of our Design and Application Guide

::
I have a TTDM monitored TT1000. Will I need a separate panel to cover the extension to the new Comms room?
::
No. Each TTDM panel can monitor upto 1500 metres of sensing cable or a mixture of sensing cables and probes. We can cover the new area as an extension of the existing room by adding a jumper cable and weighted length to the end of the circuit. We can also add a TTSIM (slave controller) so that the Comms room is monitored as a new circuit on the same master TTDM panel.

::
In a recent Health and Safety report our elevator pit was considered a weak spot due to water ingress and the potential of leaks from the hydraulic lift equipment
::
Installing a AT-SZA or AT-DIM panel connected to a AquiTron™ AT-OPSEN optical sensor would detect both water and hydraulic oil. The AT-OPSEN has an IP67 rating for this type of environment.

::
As a government agency we are required to meet the highest standard of vigilance re refrigerant gas. What would the most effective method of detecting any gas leaks be?
::
A refrigerant Leak Monitor AT-RLM can monitor upto 16 individual sensors. The unit is able to detect elements of refrigerant gas in the air from 1ppm to 1200ppm. Alarm levels can be set to give early indication meeting the HSE minimum exposure limits and the BS and EN standards

::
What is the expected life of the TraceTek cables?
::
Based on accelerated aging, TraceTek sensing cables have an expected life well above 20 years. From a practical consideration mechanical damage chemical exposure (tripping the TT5000 series, or fouling TT1000 or TT3000) are most likely to determine the life under use conditions.

::
How can we test the TraceTek TT5000 cable to ensure that is working?
::
You can bend the cable to stimulate a solvent or fuel leak. Bending the cable simulates the swelling of the conductive inner jacket that occurs in the cable when it comes in contact with solvent/fuels. When the cable is returned to its normal shape (unbent) the system will return to normal.
Click here to down load Installation & Testing Instructions manual for TT3000 & TT5000

::
Do you repair TraceTek cables if the customer is having a continuity problem?
::
No, if you are having a continuity problem when you first install the system, we will test the cable and replace it at no charge, but if the customer damages the cable, it is their responsibility.

::
If an engineer asks "Is there a difference between TT1000 and TT3000?"
::
Obviously, TT1000 and TT3000 have the same basic construction. However, TT3000 is the industrial grade product that we have tested and rated for chemical exposure. TT1000 has easy to use plastic connectors, and is intended for use in commercial buildings. TT3000 is available in modular lengths with factory-installed, low profile metal connectors, and comes with heat shrinkable tubing to cover the connectors (which will provide extra protection that the plastic connectors wouldn’t). TT3000 is also available on bulk reels for installation in double containment piping; connectors are installed at access point (after cable installation) using TraceTek connector kit.

::
How do you clean a TraceTek cable?
::
TT1000 and TT3000 can be cleaned on the top rack of the dishwasher (join the male + female connectors together, ensuring that on the TT1000 cable the orange "slip fit" ‘O’ ring is still fitted as these often fall out in normal handling, cover the connectors with plastic bags as a final precaution to stop water getting in). TT500 and TT5000 series cables cannot be cleaned of oil.

::
What is the classification for TraceTek cables? (TT5000, TT3000)
::
TraceTek cables are designed for C1D1 areas and are intrinsically safe

::
In a sludge line, can TraceTek sensing cable be spliced?
::
TT5000 series cables can be spliced in the field using TraceTek connector kits (installer must be trained). However, we sell sensing cables with factory installed connectors in modular 0.3, 1.5, 3, 4.5, 7.5, 15, & 30 metre lengths. Except for installations in double contained piping, it is usually better to use the modular cables with pre-installed connectors. Replace the whole section, disconnecting at each end and reconnecting the new length.

::
I want to use the TT1000 series cable to detect a water/propylene glycol mixture? (60/40 or 50/50 mixture) Will the cable detect the leak? Will the leak damage the cable?
::
As long as the liquid is conductive (and any water based solution will be) the TT1000 cable will detect the leak with no problem. Both TT1000 and TT3000 use fluoropolymer materials and so there will be no negatively affected by glycols of any strength.

::
Can the TraceTek TT5000 cable be re-used after it detects a leak?
::
No, you must replace the section that detected the leak.

::
When I hit the test button on my TTB-MA module, all I get is a light signal, but I am not getting any alarm?
::
The system is already in an alarm mode, or has a cable continuity problem. After the system goes into alarm and the reset button is pressed, the buzzer will not go off until the fault is cleared. The buzzer will only go off if the test button is pressed and the cable is intact and not sensing a leak that has already been acknowledged.

::
What is the wire that runs through the middle of the TT1000 and TT3000?
::
The wire inside is not part of the TraceTek detection circuit. It is a backbone for the sensor only. [some what proprietary].

::
What can you use to connect two series lengths of TraceTek cable to wire through the wet areas?
::
Use jumper cables, and we recommend using a weighted length to separate meter readings. Jumper cable does not added significantly to the total circuit length until 300 metres of jumper (will equal 1 metres of sensor cable.

::
Need specs on TT-PTB-1000 calibrator box. Expecting resistance value(s), and +/- limits.
::
The TraceTek Portable Test Box does not have a specification or data sheet. It is used to test TraceTek cables for breaks and the presence and location of water (liquids) and contamination on the cables.

::
What is the warranty on TraceTek?
::
One year from date of purchase on cables, modules and components.

::
In specs for TraceTek, it shows a four conductor jumper cable wire (air plenum cable). What is it?
::
The four conductor wires are colour coded to match the TraceTek cables. This jumper cable has been UL listed as plenum cable, so it may be used in plenum spaces without conduit.

::
This is for use in C1D2 area, how do you connect the sensing cables to set the system up in accordance with approvals? (specific junction box, stc.)
::
The sensing cable operates at low voltage, and when driven by intrinsically safe output circuits, may be located in Class I Division 1 (C1D1) hazardous locations. The alarm module is normally located in an ordinary area (although the TTG and TTA panels may be located in a C1D2 area). Consult the product data sheets for specific approvals information on each product.

::
Can we bury TraceTek TT3000 outside underground?
::
You can use TT3000 for outdoor applications? but it must be installed in an environment protected from the elements (for example, under the cladding on insulated piping). Without protecting it form the elements, normal ground water, rain, or contaminants may cause the cable to go in to alarm.

::
Does your fuel sensor detect vapours?
::
It will go into alarm if the atmosphere is saturated with fuel vapours.

::
Can TT3000 withstand 2% hydrochloride solutions?
::
The TT3000 cable is a fluoropolymer construction and very resistant to most chemicals: the data sheet provides some data on chemical resistance. Cable performance will not be impaired if the exposure is of limited duration: however, after prolonged exposure (weeks) it would be prudent to replace sections exposed to ensure maximum effectiveness.

::
What are the classifications for control panels?
::
TTA and TTG have outputs rated as intrinsically safe, so sensing cable connected the a TTB or TTDM may be located in a C1D2 areas. However, a zener barrier is required if sensing cable will be located in a C1D1 area. (see Product Selection Guide H)

::
Is there a maximum circuit length you can run off of a TTC sensing module?
::
Our published rating is 50 ft of cable. Our test data shows that it will work with up to 330 ft/100 meters of sensing cable (jumper cable is not counted as part of the circuit length). However, if that much length is involved, it is usually advisable to either have additional sensing circuits, or use a locating system.

::
With TT1000, does the main box with display include the map adjacent to the panel?
::
The graphic map is an integral part of the system. However, since it must show the layout, it must be created after the TraceTek system is installed. This service is normally performed by the TraceTek installer or specialist installer partner (it should be a paid-for line item on the bill of materials for the TraceTek system).

::
Are there caulks or putty’s that could potentially damage the TT1000 cable?
::
These materials are unlikely to damage the cable, however if they are conductive they can cause a leak alarm.

::
I keep receiving a service req'd alarm on my TTDM-PLUS. I tried to adjust the sensitivity of this, but the sensitivity menu is not available on the unit. What do I do?
::
(a) You are probably getting the Service Required Alarm for a reason. If this is a TT1000 cable in a computer room floor, check where the cable passes by air handlers. Carbon black dust from drive belt wear can collect on the cable. Use denatured alcohol on a clean rag to clean the cable at these points., you could also remove the cable and wash it on the top shelf of a dishwasher, connect both connectors together.
(b) If the cable is a TT3000 cable inside a double contained pipe, check for the presence of condensate from moist air. You can usually find it under the cap at access point risers. The pipe should be dehumidified by blowing dry air or nitrogen into the pipe until the leakage current displayed on the panel reads less than reasonable. Then ensure the pipe sealing system is good and trap the dry air or nitrogen in the pipe before sealing it.

To change the Sensitivity (Leak sensitivity) of the TTDM-PLUS panel,

1. Press the Down-Arrow key
2. Push the Down-Arrow key until Sensitivity is displayed
3. Press the Enter key
4. Push the Down-Arrow key until you reach the sensitivity level you want. IMPORTANT: Do not use the TT500x level unless you have TT5000 cable attached to the panel.
5. Push the Enter key on the selected choice
6. Press the Esc key until you navigate back to the main menu.


::
To access the SIM Status screen to see the leakage current level (displayed as "Current: XXµA"):
::
(a) In normal display mode, use the Left or Right Arrow keys to select the SIM channel of interest. (If you only have one cable connected to the TTDM, there will be only one selection.)
(b) Press the Down-Arrow key to access the detailed status information.
Click here to download a copy of the I/O manual for the TTDM-PLUS panel.

::
Can plastic connectors be connected to metal connectors?
::
Yes, TraceTek makes adaptors that will allow you to convert metal to plastic and vice versa. These adaptors will also allow you to convert from male to female as well. So, it is possible through use of an adaptor to convert a female plastic connector to a male metal connector using a TT Adaptor-F/PC-M/MC.

::
On a TTDM controller does the 4-20 output latch with the mA correlating to the leak location until the discrete leak relay output is reset via the control panel?
::
No. The 4-20mA output simply changes the current with the changing conditions sensed by the Controller. If the leak were to move, the 4-20mA output would change - relaying this to the TTDM - which would display the new leak location as "Re-Alarm nn mt" or "Re-Alarm [nnnn]" if a new leak occurs some distance from the original leak.

::
At what PPM will TT5000 cable sense a leak for crude oil. There may be some leakage into the surrounding soil already and we want only to alarm if there is a leak from the pipe.
::
Our hydrocarbon sensor cables will not respond to contamination less than 25000 ppm, which is about the maximum level that can be dissolved in water. In a case with possible existing soil contamination, the problem may be more complex than that. If there is free fuel in the soil, then we only require a few millilitres in contact with the cable to cause an alarm. One scenario is that the soil is cleaned up to a depth below the sensor cable installation, but some contamination exists below that. If the ground water level ever rises to the sensor, it will push the fuel up with it and then cause an alarm.

::
How many TT-MBC-PC 's can be connected in series to create branches?
::
The total system length is a combination of cable and any other device connected to the TTDM-PLUS or SIM-1 which adds resistance to the circuit. Each Modular Branch Connector (MBC) adds. 9 m (30 ft) to the length of the circuit due to its internal resistance (4.5 mtrs). per outgoing branch). As long as the combination of cable and MBC’s does not exceed 1,500 metres on a TTDM-Plus or SIM-1 module, you can connect as many as needed.

::
Will new TT1000 cable work with an old controller, model TTB-FA? Is there a dealer in Atlanta?
::
Yes, the TT1000 leak detection cable will work with TTB-FA monitoring panel.


 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back to the top

 

 

 

 

 

 

 

 

 

 

 

 

 

Back to the top

 

 

 

 

 

 

 

 

 

 

 

 

 

Back to the top

 

 

 

 

 

 

 

 

 

 

 

 

 

Back to the top

 

 

 

 

 

 

 


 © 2007 Aquilar Ltd. All rights reserved | Privacy Policy | Links